facebook

Schneider PM5350 Power and Energy Meter

 

Features

  • Easy to install
  • Easy to operate
  • Easy circuit breaker monitoring and control
  • System status at a glance
  • IEC 62053-22 class 0.5S accuracy for active energy
  • Power Quality analysis

Introduction Schneider PM5350 Power and Energy Meter

The Schneider PM5350 Power Meter offers electrical installation measurement capabilities in a single 96 x 96 mm unit. Three-phases and neutral can be monitored simultaneously using a bright, anti-glare display with large characters and backlighting. Menus are intuitive and the meter supports English, Chinese, Hebrew, and Spanish languages. Its compact size and high performance make the PowerLogic PM5350 sereis suitable for many applications.

Đồng hồ đa năng Schneider PM5350

Schneider PM5350 Power and Energy Meter

Features Schneider PM5350 Power and Energy Meter

Easy to install

  • Mounts using two clips, no tools required. Ultra compact meter with 44 mm depth connectable up to 480 V L-L without voltage transformers for installations compliant with category III, as per IEC 61010-1. See specification table for UL voltage limits.

Easy to operate

  • Intuitive navigation with self-guided, language selectable menus, six lines, four concurrent values. Two LEDs help confirm normal operation.

Easy circuit breaker monitoring and control

  • Two relay outputs (high performance) to command most circuit breaker coils directly. Monitored switches can be wired directly without external power supply.

System status at a glance

  • Bright, anti-glare, backlit display plus two LEDs; orange for energy pulse or alarm and green for heartbeat/communications indication.

IEC 62053-22 class 0.5S accuracy for active energy

  • Accurate energy measurement for cost allocation.

Power Quality analysis

  • The PM5350P offers THD and TDD measurements as standard. Total Demand Distortion is based on a point of common coupling (PCC), which is a common point that each user receives power from the power source. The TDD compares the contribution of harmonics versus the maximum demand load. In addition, it has individual harmonics (odd) measurement up to 31st harmonics. These types of power quality parameters help to identify the source of harmonics that can harm transformers, capacitors, generators, motors and electronic equipment.

Benefits

System integrators’ benefit

  • Ease of integration
  • Ease of setup
  • Cost effectiveness

Panel builders’ benefit

  • Ease of installation
  • Cost effectiveness
  • Aesthetically pleasing
  • Simplified ordering

End users’ benefit

  • Ease of use
  • Precision metering & sub-billing
  • Billing flexibility
  • Comprehensive, consistent and superior performance

Applications

  • Panel instrumentation.
  • Cost allocation or energy management
  • Electrical installation remote monitoring
  • Sophisticated alarming
  • Circuit beaker monitoring and control

Specifications

Power quality analysis Total demand distortion
total harmonic distortion
Device application Power monitoring
Type of measurement Current
Voltage
Frequency
Power factor
Energy
Phase angle
Apparent power
Active power
Reactive power
supply voltage 90…450 V AC 45…65 Hz
100…300 V DC
Network frequency 50 Hz
60 Hz
[In] rated current 5 A
1 A
type of network 1P + N
3P + N
3P
Maximum power consumption in VA 11.9 VA
Ride-through time 100 ms 120 V AC typical
400 ms 230 V AC typical
50 ms 125 V DC typical
Display type Monochrome graphic LCD
Display resolution 6 lines
Sampling rate 32 samples/cycle
Measurement current 5…9000 mA
Analogue input type Current 0.05…9 A (impedance <= 0.3 mOhm)
Voltage (impedance 10 MOhm)
Measurement voltage 35…760 V AC 45…65 Hz phase to phase
20…400 V AC phase to neutral
Frequency measurement range 45…70 Hz
Number of inputs 4 digital
Measurement accuracy Current +/- 0.5 %
Voltage +/- 0.5 %
Frequency +/- 0.05 %
Power factor +/- 0.5
Active energy +/- 0.5 %
Reactive energy +/- 2 %
Active power +/- 0.5 %
Apparent power +/- 0.5 %
Apparent energy +/- 0.5 %
Reactive power +/- 2 %
Accuracy class Class 0.5S active energy conforming to IEC 62053-22
Class 0.5 active energy conforming to IEC 61557-12
Class 3 reactive energy conforming to IEC 62053-23
Class 2 reactive energy conforming to IEC 61557-12
Class 0.5 power conforming to IEC 61557-12
Number of outputs 2 relay
Information displayed Tariff (4)
Communication port protocol JBUS
Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds
Communication port support Terminal block: RS485
Data recording Min/max of instantaneous values
Alarms
Connections – terminals Voltage circuit: screw terminal block4
Control circuit: screw terminal block2
Current transformer: screw terminal block6
Input/output circuit: screw terminal block6
Relay output: screw terminal block4
Ethernet network: RJ45 connector
Mounting mode Flush-mounted
type of installation Indoor installation
Standards IEC 61010-1
Product certifications CE
CULus
Width 96 mm
Depth 44 mm
Height 96 mm
Net weight 0.25 kg

 

Brand

Review Schneider PM5350 Power and Energy Meter

5 0% | 0 review
4 0% | 0 review
3 0% | 0 review
2 0% | 0 review
1 0% | 0 review
Review Schneider PM5350 Power and Energy Meter
Choose a image
0 character ( Minimum of 10)
    +

    Very poor Not that bad Average Good Perfect

    There are no reviews yet.

    No comments yet

    RECENT PRODUCT

    hotline techmaster
    Hotline: 0936 532 379
    zalo techmaster Zalo: 0936 532 379 messenger techmaster Nhắn tin Facebook
    support techmaster